Contact: sales@haomai.net
Composite Error: In a steady state, the root mean square value of the difference between the instantaneous value of the primary current and the instantaneous value of the secondary current multiplied by the rated current ratio (transformation ratio).
Error Curve: When a short-circuit current flows through the primary winding of a protective current transformer, the transformer transmits current information to the secondary side. To ensure the correct operation of the relay protection device, the transformer must have a certain accuracy, i.e., the composite error does not exceed the limit values (5% and 10% are the two common limits). The relationship curve between the primary current multiple and the secondary load while keeping the error limit constant is generally referred to as the error curve.
Note: When a CT is under overcurrent conditions, the secondary current is no longer a sine wave due to the distorted waveform of the excitation current. The CT error characteristics cannot be specified directly by the current error and phase difference, and the composite error must be used instead.
Accuracy Limit Factor (ALF, or Kalf): In a steady state, the ratio of the maximum primary current value (Ipal) that a CT can carry while meeting the composite error requirement to the rated primary current (Ipn), i.e., Kal=Ipal/Ipn.
The standard values of the accuracy limit factor are generally 5, 10, 20, 30, 40.
For example, if a CT nameplate is marked 10P30, the accuracy class is 10P and the accuracy limit factor is 30. When the short-circuit current does not exceed 30 times the rated current (IN), the composite error of the CT will not exceed 10%.

△ 5% Error Curve

△ 5% Error Data
Where:I1M – Maximum short-circuit current on the primary side;I1N – Rated primary current;I2N – Rated secondary current;I2 – Secondary current;I0 – Excitation current;Z2 – Secondary winding impedance;E0 – Induced electromotive force of the secondary winding;Kn – Rated current ratio;ZB – Maximum allowable load impedance at 10% error;M – Multiple of the maximum short-circuit current on the primary side.

△ Wiring Diagram

△ Parameter Setting
The CTP-120P Transformer Tester is used for the test in this case, and the test result analysis is as follows:
Example: A CT nameplate is marked 5P10. The maximum allowable secondary impedance is 2.8Ω obtained from the 5% error curve, and the CT performance can be judged against the protection requirements by the actual measured value of the secondary impedance.
Conduct the excitation test using the CTP-120P Transformer Tester with the wiring method shown in the above figure, and fill in the actual load or rated load in the load field on the parameter setting page.

△ Accuracy Limit Factor Test Result
Note: If the measured ALF is greater than or equal to the rated value, the CT is qualified, and other tests can be carried out subsequently. If the measured ALF is less than the rated value, the CT is judged as unqualified.
Example: A CT nameplate is marked 10P20 with a transformation ratio of 1000:1, and the protection instantaneous trip setting value is 20A. How to judge the influence of ALF on the protection action?
Copyright © 2024 All rights Reserved.
备案号:鄂ICP备05010718号-1