Contact: sales@haomai.net
Protection Device: PCS-985 Generator-transformer Unit Protection Device
Test Instrument: Relaystar-7000 Digital-analog Integrated Relay Protection Tester
The diagram below shows the generator-transformer unit system of a power plant. The main transformer is a three-winding transformer, and the low-voltage side of the station transformer has a double-branch structure. The generator-transformer unit differential protection includes four branch currents, namely the 220kV side current I1, 110kV side current I2, high-voltage station transformer high-voltage side current I3 and generator neutral point side current I4 of the main transformer. The polarity terminals of TA on each side are shown in the figure, and the reference direction of each side current is defined as positive when flowing into the generator-transformer unit.

△ Generator-transformer Unit System Diagram

△ Differential Operating Characteristic Diagram
Percentage Differential Protection Operating Equation:

This paper introduces how to use the Relaystar-7000 Digital-analog Integrated Relay Protection Tester to commission the PCS-985 generator-transformer unit differential protection.
|
Serial Number |
Setting Name |
Value |
Serial Number |
Setting Name |
Value |
|
01 |
Rated Capacity of Main Transformer |
360MVA |
09 |
Secondary Side of Generator TA |
5A |
|
02 |
Primary Rated Voltage of High-voltage Side |
242kV |
10 |
- |
- |
|
03 |
Primary Side of High-voltage Side TA |
1250A |
11 |
Generator-transformer Unit Differential Pickup Value |
0.4Ie |
|
04 |
Secondary Side of High-voltage Side TA |
1A |
12 |
Generator-transformer Unit Differential Instantaneous Value |
5Ie |
|
05 |
Rated Capacity of Generator |
330MVA |
13 |
Initial Slope of Percentage Restraint |
0.1 |
|
06 |
Power Factor of Generator |
0.94 |
14 |
Maximum Slope of Percentage Restraint |
0.7 |
|
07 |
Primary Rated Voltage |
20kV |
15 |
Differential Instantaneous Protection Enable |
1 |
|
08 |
Primary Side of Generator TA |
15000A |
16 |
Percentage Differential Protection Enable |
1 |
In the "Press Plate Settings", set the "Generator-transformer Unit Differential Protection" soft press plate to "1", set the "Maintenance" hard press plate to "1", and disconnect the "Trip Output" hard press plate.
The YD11 current phase compensation of the generator-transformer unit differential protection in the PCS-985 device adopts the method of compensation from the Y side to the Δ side:

△ PCS-985 Phase Conversion Vector Diagram and Formula
For the YD-11 main transformer connection mode, the PCS-985 device adopts the method of phase correction from the main transformer high-voltage side currents A-B, B-C, C-A to the generator neutral point side. During the differential protection test, currents are injected from the high-voltage side and the generator neutral point side respectively.
The corresponding relationship of the injected currents between the high-voltage side and the neutral point side is: A - ac, B - ba, C - cb.
When a current IA=
∠0∘, IB=0, IC=0 is injected into the high-voltage side, the converted currents are IA′=1∠0∘, IB′=0, IC′=1∠180∘.The corresponding currents injected into the low-voltage side are Ia=1∠180∘, Ib=0, Ic=1∠0∘.
∘.
△ PCS-985 Differential Wiring Diagram


△ Generator-transformer Unit Balancing Current Parameter Settings
Percentage Differential Boundary TestConduct the test according to the table below. Note that the high-voltage side current needs to be divided by 1.732 when converted to the rated current during the test. The test data are shown in the table below.
|
Serial Number |
Current on Side 1 (A) |
Current on Side 2 (A) |
Restraint Current Ir (A) |
Differential Current Id (A) |
|
A |
Ie |
Ie |
Ie |
Ie |
|
1 |
1.19 |
1 |
1.689 |
0.5 |
|
2 |
1.87 |
1.57 |
3.378 |
1 |
|
3 |
3.4 |
2.85 |
6.756 |
2 |
|
4 |
5.13 |
4.31 |
10.134 |
3 |
|
5 |
7.12 |
5.98 |
13.512 |
4 |
|
6 |
9.41 |
7.98 |
16.89 |
5 |
Based on the restraint current Ir and differential current Id from the above test data, the generator-transformer unit differential percentage boundary curve can be plotted.

Copyright © 2024 All rights Reserved.
备案号:鄂ICP备05010718号-1